Cool Cell™ is Zomeworks Corporation's passive climate-control system: water reservoirs in the ceiling connect to roof-mounted radiator/absorbers. In summer, the water absorbs interior heat during the day and radiates it to the night sky. In winter, a pump circulates water through the same roof panels for solar gain. No electricity for cooling, no refrigerants, no compressor.
The system grew out of 31 years of passive-energy product development and earlier Cool Cell variants using custom-molded polyethylene bottles, five-gallon water bags, and two-liter soda bottles. The architectural brochure (circa 2002) describes five operating modes:
- Summer day: Water in the ceiling acts as a heat sink, absorbing interior heat. Roof-mounted radiator/absorbers are too hot from the sun for thermosiphon circulation — no solar gain enters the system.
- Summer night: Radiator/absorbers cool by radiation to the sky; thermosiphon circulation begins and continues overnight, recharging the ceiling reservoir with cool water.
- Winter day: A low-power pump circulates water through the roof for solar gain. Closing aluminum louvers allows maximum heat storage without overheating the space.
- Winter day with south-wall absorber: For colder climates, a south-wall absorber circulates by natural thermosiphon (no pump). Since it sits below the ceiling reservoir, it cannot drain back and must be freeze-tolerant.
- Winter heating only: In mild-summer climates, a freeze-tolerant south-wall absorber provides heating by thermosiphon with no pump.

Conceptual sketch of the Cool Cell's seasonal operating modes. Top right: summer day — sun drives roof temperature too high for circulation; ceiling tank absorbs interior heat. Bottom left: summer night — roof radiates to sky, thermosiphon recharges tank with coolth. Bottom right: winter — sun drives circulation through roof collector into storage tank.
The brochure makes the case directly: water weighs half as much as masonry and stores twice the heat per volume. It is non-toxic, non-flammable, readily available, dense, thermally conductive, and has high specific heat. Its high heat of vaporization allows "supercharging" cooling by evaporation from a wet radiator. The downside — high heat of fusion and expansion on freezing — is managed by drain-back in winter rather than antifreeze.
The October 2002 "Work Leading Up" notes trace the engineering path:
- US Patent 4,913,985 (1990) — Battery Temperature Regulation System: The first patent in the Cool Cell lineage, designed for telephone company battery cabinets. A flat radiator above a water container in the cabinet; water circulates by thermosiphon. Zomeworks sold thousands of these units, commercially proving the night-sky radiative cooling principle before attempting the architectural market.
- US Patent 5,070,933 (1991) — Temperature Regulating System: Added an insulation layer inside the water container that stratifies cool/warm water — cold night-cooled water stays at the top, warm room-temperature water stays at the bottom. This is the ceiling-mounted insulated water container that became the Cool Cell ceiling reservoir concept.
- US Patent 5,316,872 (1994) — Passive Cooling System: Moved the radiator definitively to the exterior/roof of the enclosure, with symmetric parallel conduits creating balanced thermosiphon flow. The "pair of symmetric conduits" visible in the Cool Cell diagrams traces directly to this patent.
- US Patent 5,513,696 (1995): The corrugated-roof version for buildings — a system of blow-molded plastic containers with a corrugated heat-exchanger portion that mates directly to roll-formed metal roofing. Water circulates by thermosiphon between the interior reservoir and the roof. This patent, filed in 1995 by Baer with Zomeworks as assignee, predates the brochure's "31 years" claim; Dave Harrison's concurrent patent application (08/277,925) documents his parallel water-container work at Zomeworks. The 1995 system was later refined into the 2001 Cool Cell patent (US 6,357,512 B1).
- Di-thermal walls with boogie valves: Shawn Buckley's idea of passive heaters with collector and tank at the same level, using floating plastic check valves (named "boogie valves" by Joe Minella because the plastic balls could be seen boogieing through clear pipe). These worked for both heating and cooling but leaked slowly and were complicated to reverse seasonally.
- Ceiling tanks: Bill Mingenbach suggested 8″ PVC pipes overhead. Combined with rooftop radiators (switched to in August 1999), these proved superior to wall radiators — roofs radiate better than walls, as confirmed by Cramer and Newbauer's 1964 work.
- Heated vs unheated plates: Bristol Stickney and Baer's matched-plate experiments (detailed separately) proved that night radiation can exceed 9.5 watts per square foot.
The brochure estimates for a storage building allowed to fluctuate between 40°F and 95°F:
- Cooling season savings: ~10 kWh/ft²
- Heating season savings: ~25 kWh/ft²
- At $0.10/kWh: $3.50/ft²/year savings, plus eliminating the capital cost of a compressor
Unlike most modern technology, Cool Cell systems are transparent in function. Flow patterns explain themselves. Every part is simple, every connection easy. No anti-freeze, no heat exchangers, no glass, no collector boxes, simple controls. Rubber connectors can be pushed on by hand. Cuff connectors self-seal and need no tools.